GAS SUPPRESSION

Compare four agents on the metrics that matter.

Inergen, FK-5-1-12 (Novec 1230), FM-200 and CO₂ — side by side on safety, hold time, GWP, room size and code. Select the right agent for the room and the people in it.

AT A GLANCE

Selection guide

Pick the agent that fits the protected volume and the people who occupy it. Each card links to its full solution page.

FULL COMPARISON

Side-by-side properties

PropertyInergenFK-5-1-12 (Novec 1230)FM-200 (HFC-227ea)CO₂
ClassInert gas (clean agent)Halocarbon (clean agent)Halocarbon (clean agent)Inert gas (asphyxiant)
CompositionN₂ 52%, Ar 40%, CO₂ 8%C₆F₁₂O fluoroketoneC₃HF₇ hydrofluorocarbon100% CO₂
Discharge time60 s (typical)10 s10 s60–90 s (high-pressure)
Hold time10 min minimum (NFPA 2001)10 min minimum10 min minimumUntil ventilated; sealed enclosure
Design concentration37–43% by volume4.2–5.5% by volume6.7–9% by volume34–75% by volume
NOAEL / LOAEL43% / 52%10% / >10%9% / 10.5%Toxic at design conc.
Personnel-safe?Yes (above design conc. up to LOAEL)Yes (large safety margin)Yes (above design conc. to LOAEL)No — requires evacuation + lock-out
Ozone-depletion (ODP)0000
Global Warming Potential (GWP)0<13,2201
Atmospheric lifetimeHours–days3–5 days36 yearsCenturies
Cylinder storage volumeLargest (high-pressure inert)Smallest among clean agentsSmallMid
StandardsNFPA 2001 · ISO 14520 · IMO MSC.1/Circ.1432NFPA 2001 · ISO 14520NFPA 2001 · ISO 14520NFPA 12 · IMO MSC.1/Circ.1318
Best-fit applicationsData centre white-space, telecom, control rooms, museums, FPSO electrical roomsData centre white-space, MEP rooms, electronics, light hazardData centre white-space, server rooms, light electricalTurbine enclosures, paint stores, machinery spaces, marine engine rooms

Properties shown are typical design values; final concentrations and discharge timing are sized to project HAZOP, room volume, leakage, hold-time requirements and AHJ approval.

STANDARDS

Compatible codes

CLEAN AGENT

NFPA 2001 · ISO 14520

Standard for clean-agent fire-extinguishing systems. Applies to Inergen, FK-5-1-12 and FM-200.

CO₂ SYSTEMS

NFPA 12 · IMO MSC.1/Circ.1318

Standard for CO₂ fire-extinguishing systems and IMO guidelines for fixed CO₂ systems on board ships.

MARINE INERT GAS

IMO MSC.1/Circ.1432

IMO guidelines for the maintenance and inspection of fixed fire-suppression systems on board ships.