Skip to Content
SUPPRESSION — INERT GAS

IG-541 and IG-55 inert-gas suppression.

Inergen (52% N₂, 40% Ar, 8% CO₂) and Argonite (50% N₂, 50% Ar) for occupied data centres, control rooms, archives and switchgear — total flooding without ozone or global-warming impact.

37–43%
Design concentration
60 s
Discharge time
TECHNOLOGY

How Inert Gas works.

Inert-gas systems suppress fire by lowering the oxygen concentration in the protected space from 20.9% to between 12.5% and 14.5% — below the level that sustains most combustion, but still high enough for a brief evacuation. Hawk Marine engineers, fabricates and FAT-tests Inergen and Argonite total-flooding systems for occupied spaces where clean-agent residue would damage electronics or paper.

Storage cylinders are charged at 200 or 300 bar; discharge is metered through high-pressure selector and pilot valves to deliver 95% of the design quantity within 60 seconds, NFPA 2001 nominal. Cylinder banks are typically located in a dedicated agent room and piped via Schedule 40 / 80 carbon-steel manifolds to ceiling-level discharge nozzles.

Because the agents occur naturally in the atmosphere, IG-541 and IG-55 have zero ozone-depletion potential, zero direct global-warming potential, and an atmospheric lifetime measured in days. They are the agents of choice when a project specification rules out fluorinated chemicals.

SPECIFICATIONS

Engineering basis.

Composition (IG-541)52% N₂, 40% Ar, 8% CO₂
Composition (IG-55)50% N₂, 50% Ar
Storage pressure200 bar or 300 bar
Cylinder sizes80 L, 140 L (high-pressure)
Design concentration37–43% (hazard dependent)
Maximum O₂ reductionto 12.5–14.5%
Discharge time (95%)60 s nominal
Hold time10 min minimum (typical)
ODP / GWP0 / 0
Atmospheric lifetimeDays
StandardsNFPA 2001, ISO 14520, EN 15004
APPLICATIONS

Where it fits.

Data centres & server rooms

White space, MDF/IDF rooms, switchgear — agent leaves no residue on electronics.

Control rooms & SCADA

Operator-occupied process control, refinery and FPSO control rooms, traffic and grid centres.

Archives & museums

Paper, film, art — agent does not stain or wet exposed media.

Marine machinery enclosures

FPSO E-houses, switchboard rooms, navigation equipment compartments.

WHY THIS AGENT

Engineered advantages.

Safe for occupants

At design concentration, oxygen remains in the breathable range — people can self-evacuate.

Zero environmental impact

Atmospheric gases — no ozone depletion, no global-warming potential.

No residue

Agent vents on its own — equipment back online without clean-up.

Long service life

Cylinders qualify for re-test cycles up to 50 years — lower lifecycle cost vs. halocarbons.

HAWK MARINE SCOPE

What you get from us.

01
Hydraulic calc, hazard analysis, room integrity
02
Skid & cylinder bank fabrication in Singapore
03
FAT, third-party witness, documentation pack
04
Site install, commissioning & AMC
DELIVERED

Recent projects.

CASE STUDY

BW Energy Maromba FPSO

Inergen suppression for the FPSO equipment rooms — engineering, fabrication and FAT in Singapore.

VIEW PROJECTS →
CASE STUDY

UOB Data Centre, Singapore

Inergen with VESDA aspirating detection on the bank’s primary data hall.

VIEW PROJECTS →
COMPARE

Where this fits

COMPARE AGENTS
See this agent side-by-side with Inergen, FK-5-1-12, FM-200 and CO₂
View matrix →
SCOPE A SYSTEM

Bring us your hazard and code basis.

We will respond with cylinder count, hydraulic basis and a delivery programme. Plus the comparison matrix if you want to test alternatives.

Talk to engineering Compare agents