Halocarbon clean agents — FK-5-1-12 (Novec 1230) and FM-200.
Fast-discharge, electrically non-conductive clean agents for sensitive electronic and electrical risks. Designed to NFPA 2001 and ISO 14520, sized to the room.
Heat absorption + radical inhibition
Halocarbon clean agents extinguish fire by absorbing heat (cooling) and through chemical chain-breaking. Discharge is rapid — typical 10-second design — and the agent is electrically non-conductive, leaves no residue and evaporates without any clean-up.
Discharge in 10 seconds
Rapid total flooding of the protected volume; design concentration achieved within the standard 10-second window.
Electrically non-conductive
Safe to discharge on energised electronics, server cabinets, switchgear and control panels.
No clean-up
Agent vapourises completely — no powder, no foam residue, no water damage to electronics.
At a glance
| Agent variants offered | FK-5-1-12 (Novec 1230, 3M) and FM-200 (HFC-227ea) |
| Class | Halocarbon clean agent |
| Discharge time | 10 seconds (design) |
| Hold time | 10 minutes minimum (NFPA 2001) |
| Design concentration | FK-5-1-12: 4.2–5.5% · FM-200: 6.7–9% |
| NOAEL | FK-5-1-12: 10% · FM-200: 9% |
| Personnel-safe? | Yes — above design concentration to LOAEL |
| Ozone-depletion (ODP) | 0 |
| Global Warming Potential | FK-5-1-12: <1 · FM-200: 3,220 |
| Atmospheric lifetime | FK-5-1-12: 3–5 days · FM-200: 36 years |
| Cylinder pressure | 25 bar (FK-5-1-12) / 25–42 bar (FM-200) |
Where halocarbon clean agents fit
Data centre white space
Server rooms, telecom rooms, edge cabinets — fast knock-down with no water damage.
Electrical & control rooms
MCC rooms, switchgear, UPS rooms — safe discharge on energised equipment.
Light-hazard archives
Document stores, museums, art-storage vaults where water-based suppression is unacceptable.
Compatible codes
Hawk Marine’s clean-agent designs are HAZOP-aware, hold-time verified, and submitted to the AHJ with full hydraulic calculations and discharge-room integrity testing.